Performs the following verifications on all inverters in the system
in order to check the correct compatibility between the inverter and
the photovoltaic field which flows into:
Limits on the voltage: The
minimum and maximum values of the output voltage of the photovoltaic
generator under the operating conditions must be contained in the
range of MPP of inverter, also the maximum voltage produced by the
generator must be less than the maximum voltage allowable from the
inverter. The maximum voltage of the generator is the string voltage
at the minimum operating temperature of the photovoltaic module.
Limits on the current: The
short-circuit current of the photovoltaic generator must be less than
the maximum current permissible by the inverter.
Limits on power: The sizing
factor of power must be between the minimum and maximum allowable
(see Properties|Settings).